Three Phase Power Calculator: kW, kVA, kVAR and Current

Enter the line voltage (415 V in India), current and power factor to get kW, kVA and kVAR, or enter kW to get the current. Star and delta phase values are shown too.

Power

12.22kW

Apparent power
14.38 kVA
Reactive power
7.57 kVAR
Phase voltage
239.6 V
Phase current
20 A

Assumes a balanced load on all three phases.

Show working
  1. P = √3 × 415 × 20 × 0.85 = 12,220 W
  2. S = √3 × 415 × 20 = 14,376 VA

How to use

  1. Choose whether to find power or current.
  2. Enter line-to-line voltage, current (or kW) and power factor.
  3. Choose star or delta to see phase voltage and current.

Good to know

For a balanced three-phase load: P = √3 × V(line) × I(line) × PF; apparent power S = √3 × V × I; reactive power Q = √(S² − P²). Current for a known load: I = P ÷ (√3 × V × PF).

Star (Y): phase voltage = line voltage ÷ √3 (415 V → 240 V), phase current = line current. Delta (Δ): phase voltage = line voltage, phase current = line current ÷ √3.

For a motor, P here is the electrical input; shaft output is lower by the motor efficiency (often 85–95%). Unbalanced loads need each phase worked separately.

Questions

How many amps is a 10 kW three-phase load?

At 415 V and PF 0.85: 10,000 ÷ (1.732 × 415 × 0.85) = 16.4 A per line.

What is the formula for three-phase power?

P = √3 × V(L-L) × I × PF.

Why √3?

Because the three phase voltages are 120° apart, line voltage is √3 times phase voltage in a star system.

What is the phase voltage of 415 V supply?

415 ÷ 1.732 = 240 V (line to neutral).

What power factor should I use?

From the equipment plate; induction motors are often 0.8–0.9 at full load.