Transformer Calculator: Turns Ratio, Primary and Secondary Current

Enter the transformer kVA rating and primary and secondary voltages. You get the turns ratio, full-load currents on both sides and, if you give primary turns, the secondary turns.

Turns ratio

9.583 : 1

Step-down
Primary current
4.348 A
Secondary current
41.667 A
Secondary turns
52.2 turns

Ideal transformer; real units have a few percent loss and voltage drop.

Show working
  1. a = 230 ÷ 24 = 9.5833
  2. Ip = 1,000 ÷ (230) = 4.348 A
  3. Is = 1,000 ÷ (24) = 41.667 A
  4. Ns = 500 × 24 ÷ 230 = 52.17

How to use

  1. Choose single- or three-phase.
  2. Enter kVA rating and primary and secondary voltage.
  3. Optionally enter primary turns to get secondary turns.

Good to know

For an ideal transformer, Vp ÷ Vs = Np ÷ Ns = Is ÷ Ip. Full-load current: single-phase I = VA ÷ V; three-phase I = VA ÷ (√3 × line voltage). A 1 kVA 230/24 V transformer carries 4.35 A on the primary and 41.7 A on the secondary.

For three-phase transformers, the ratio shown is between line voltages. Actual turns per winding depend on the star or delta connection on each side (for example an 11 kV/433 V Dyn11 distribution transformer).

Real transformers have losses and regulation, so the secondary voltage drops a few percent at full load and the no-load voltage is slightly higher. Size cables and fuses from these full-load currents with proper margins.

Questions

What is the current of a 100 kVA transformer at 433 V?

100,000 ÷ (1.732 × 433) = 133 A per phase on the LV side.

What is the turns ratio of 230 V to 12 V?

230 ÷ 12 = 19.17 : 1.

Does a step-down transformer increase current?

Yes. Power stays about the same, so lower voltage means higher current on the secondary.

How many secondary turns for 24 V if primary is 500 turns at 230 V?

500 × 24 ÷ 230 = 52 turns (plus a few for losses in practice).

Is this for an ideal transformer?

Yes. Real units have losses and a few percent voltage drop at load.